Specifications: Fluke 376 True RMS AC/DC Clamp Meter with iFlex®
Electrical Specifications
AC Current via Jaw
Range 374 and 375
376 600.0 A
999.9 A
Resolution 0.1 A
Accuracy 2% ± 5 digits (10-100 Hz)
2.5% ± 5 digits (100-500 Hz)
Crest Factor (50/60 Hz) 3 @ 500 A (375 and 376 only)
2.5 @ 600 A
1.42 @1000 A (376 only)
Add 2% for C.F. > 2
AC Current via Flexible Current Probe
Range 2500 A
Resolution 374 and 375 0.1 A (≤ 600 A)
1 A (≤ 2500 A)
376 0.1 A (≤ 999.9 A)
1 A (≤ 2500 A)
Accuracy 3% ±5 digits (5 – 500 Hz)
Crest Factor (50/60Hz) 3.0 at 1100 A (375 and 376 only)
2.5 at 1400 A
1.42 at 2500 A
Add 2% for C.F. > 2
Distance from Optimum i2500-10 Flex i2500-18 Flex Error
A 0.5 in (12.7 mm) 1.4 in (35.6 mm) ± 0.5%
B 0.8 in (20.3 mm) 2.0 in (50.8 mm) ± 1.0%
C 1.4 in (35.6 mm) 2.5 in (63.5 mm) ± 2.0%
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range.
DC Current
Range 374 and 375
376 600.0 A
999.9 A
Resolution 0.1 A
Accuracy 2% ± 5 digits
AC Voltage
Range 374 and 375
376 600.0 V
1000 V
Resolution 374 and 375
376 0.1 V
0.1 V (≤ 600.0 V)
1 V (≤ 1000 V)
Accuracy 1.5% ± 5 digits (20 – 500 Hz)
DC Voltage
Range 374 and 375
376 600.0 V
1000 V
Resolution 374 and 375
376 0.1 V
0.1 V (≤ 600.0 V)
1 V (≤ 1000 V)
Accuracy 1% ± 5 digits